01A Series, Digital Fuel Meters
GPI
| Max. Operating Pressure | Display Type | Power Source | Overall Height | Overall Width | Connection Size | Min. Flow Rate | Max. Flow Rate | Price |
|---|---|---|---|---|---|---|---|---|
| 150 psi | Digital | - | 2 3/8" | 2 1/8" | 1" | 3 GPM | 30 GPM | $361.80 |
| 300 psi | LCD | AAA Alkaline Batteries | - | - | 1" | 3 GPM | 30 GPM | RFQ |
| 300 psi | LCD | AAA Alkaline Batteries | - | - | 1" | 3 GPM | 30 GPM | RFQ |
| 300 psi | Digital | AAA Batteries | 2 1/2" | 2" | 1" | 3 GPM | 30 GPM | $318.25 |
| 300 psi | Digital | AAA Batteries | 2 1/2" | 2" | 1" | 3 GPM | 30 GPM | $333.83 |
Working Mechanism
- Turn On the 01A Series meter by either starting fuel flow or pressing the Display button.
- The meter should display the last batch or cumulative total.
- Users can hold the display button for three seconds for resetting the batch total back to zero.
- After one minute of measuring the fuel flow, the meter automatically turns Off to conserve power.
Features
- GPI 01A Series digital fuel meters are battery-powered using two AAA batteries and have a 4-digit liquid crystal display.
- They can display both batch & cumulative totals.
- The batch total reading is resettable whereas the cumulative totals reset at 9999 reading.
- These devices have an automatic On / Off mechanism for saving battery life and their magnetic sensor has an accuracy of +/- 5%.
- These motors have aluminium / nylon housing and sealed electronic circuitry containing nylon rotor, tungsten carbide shaft, ceramic bearings, ferrite signal generator & stainless steel retaining rings.
- They are factory calibrated according to the petroleum fuel.
Standards & Approvals
- FM
- CE
Frequently Asked Questions
Can we replace the batteries in GPI 01A Series digital fuel meters?
- Users can easily replace the batteries in these meters. However, users should remember that when batteries lose power or are removed, the batch & cumulative total readings reset back to zero. But the factory calibration settings are retained.
How to install these GPI 01A Series digital fuel meters?
- Remove the nozzle from the hose and wrap the hoses with thread tape without intruding on the flow path.
- Attach a hose with the selected meter's outlet port having an arrow pointed in the direction of flow.
- Fix the nozzle to the meter's other end. Use an enclosed 3/4-inch fitting if required. Tighten the connections using a wrench.
- Users can install in-line in both horizontal or vertical orientation.
- However, care must be taken that the line is full without any air for accuracy.
What is the pressure & temperature rating of these GPI 01A Series digital fuel meters?
- GPI 01A Series digital fuel meters have a pressure rating of 300 PSI (21 bar) and operating temperature ranging from 14 to 130 degrees F (-10 to 54 C).
Explore More
- BISHAMON INDUSTRIES
- BRECO
- KEYSHAFT
- DANCO
- AMERICAN METALCRAFT
- RUD CHAIN VRBK FIX/VRBK Load Rings For Welding For 90 Degree Corners
- CHICAGO PNEUMATIC Positive Clutch & Direct Drive Screwdrivers
- CHICAGO PNEUMATIC CP3030 Series Right Angle Air Die Grinders
- ANVIL 2140 Series Flush Bushings, Forged Steel
- KIPP M6 Thread Size Mini Wing Knob
- E JAMES & CO Rubber Cord Stocks
- ALL MATERIAL HANDLING Double Jacket Round Slings
- BALDOR / DODGE XT60 Heavy Duty Drum Pulleys
- STARRETT 91434 Series Duratec Band Saw Blades
Ask ChatMRO